    CommScope LazrSPEED® Plenum Distribution Cable, 12 fiber single-unit SPOOL 600 FEET brand new factory packed on wooden spool, factory shrinked NOT OLD STOCK!
    These came from a large data center, as leftovers from a project.    They are new in every way.
    I have copied/pasted the specs from the manufacturers website in relation to this product
    These are new, and as such we cannot offer a return for a new item, because it would no longer be new.    Please research and understand  the product before buying.
    Thanks for checking out our listing!
    FREE shipping in the continental USA.   This will be shipping using fedex Ground, on the spool with no additional overpacking.
    MPL Solutions, Terryville CT
    Product Classification
    Regional Availability
    Asia | Australia/New Zealand | Latin America | Middle East/Africa | North America
    Portfolio
    CommScope®
    Product Type
    Fiber indoor cable
    General Specifications
    Cable Type
    Distribution
    Construction Type
    Non-armored
    Fiber Type, quantity
    12
    Jacket Color
    Aqua
    Subunit Type
    Gel-free
    Total Fiber Count
    12
    Dimensions
    Diameter Over Jacket
    5.77 mm | 0.227 in
    Representative Image
    Click on image to enlarge.
    Mechanical Specifications
    Minimum Bend Radius, loaded
    86 mm | 3.386 in
    Minimum Bend Radius, unloaded
    58 mm | 2.283 in
    Tensile Load, long term, maximum
    200 N | 44.962 lbf
    Tensile Load, short term, maximum
    667 N | 149.948 lbf
    Compression
    10 N/mm | 57.101 lb/in
    Compression Test Method
    FOTP-41 | IEC 60794-1 E3
    Flex
    100 cycles
    Flex Test Method
    FOTP-104 | IEC 60794-1 E6
    Impact
    5.88 N-m | 52.042 in lb
    Impact Test Method
    FOTP-25 | IEC 60794-1 E4
    Strain
    See long and short term tensile loads
    Strain Test Method
    FOTP-33 | IEC 60794-1 E1
    Twist
    10 cycles
    Twist Test Method
    FOTP-85 | IEC 60794-1 E7
    Vertical Rise, maximum
    500 m | 1640.42 ft
    Optical Specifications
    Fiber Type
    OM3, LazrSPEED® 300 | OM3, LazrSPEED® 300
    Environmental Specifications
    Installation temperature
    0 °C to +70 °C (+32 °F to +158 °F)
    Operating Temperature
    -20 °C to +70 °C (-4 °F to +158 °F)
    Storage Temperature
    -40 °C to +70 °C (-40 °F to +158 °F)
    Cable Qualification Standards
    ANSI/ICEA S-83-596 | Telcordia GR-409
    Environmental Space
    Plenum
    Flame Test Listing
    NEC OFNP (ETL) and c(ETL)
    Flame Test Method
    NFPA 130 | NFPA 262
    Environmental Test Specifications
    Heat Age
    -20 °C to +85 °C (-4 °F to +185 °F)
    Heat Age Test Method
    IEC 60794-1 F9
    Low High Bend
    -20 °C to +70 °C (-4 °F to +158 °F)
    Low High Bend Test Method
    FOTP-37 | IEC 60794-1 E11
    Temperature Cycle
    -20 °C to +70 °C (-4 °F to +158 °F)
    Temperature Cycle Test Method
    FOTP-3 | IEC 60794-1 F1